Researchers Trace 60-Second Grid Frequency Dips to Battery Storage Power Checks
Tennet Germany, the largest transmission system operator[1] in Germany, has for years observed brief dips in grid frequency[2] in the European power grid every 60 seconds. The deviations were not critical to grid security, but they were clearly measurable and unusually regular, and their cause was unclear. A team led by Dirk Witthaut from Forschungszentrum Jülich, together with researchers from the University of Cologne and the Karlsruhe Institute of Technology, traced the cause to large-scale battery storage systems that check their state of charge[3] every minute. The synchronized consumption of many such devices produces measurable fluctuations, and the effect turned out to be global rather than specifically European; the team reports the findings in Nature Energy.
Since a single consumer or generator could be ruled out, the researchers concluded the cause had to be something controlled by the clock. Using the Living Lab Energy Campus research infrastructure on the Jülich campus, they installed measuring points on end devices at 80 locations and found the same periodic pattern exactly where large-scale battery storage systems ensure an uninterrupted power supply; one such system showed a spike in consumption at the start of every minute. There are no binding standards for such power checks, so manufacturers apparently each settled on a 60-second interval, and Witthaut notes that other digitally controlled appliances such as air-conditioning systems, heat pumps, washing machines and dishwashers may show similar patterns.
The demand spikes make turbines at hydroelectric power stations slow down momentarily before accelerating back to their original rotational speed, which increases wear and tear. In Ireland, where data centres with large-scale battery storage account for around a fifth of the country's electricity demand, the amplitude of the 1-minute signal quadrupled between 2016 and 2021. Witthaut says the solution is simple: distribute the checks randomly instead of always starting them at the same time.
Read the original fz-juelich.deDiscussion
Sources
-
fz-juelich.de
Mystery of 60-Second Fluctuations in Power Grids Solved