A false smoke alarm almost drowned Jane Street's only NYC datacenter

Jane Street is a trading firm, and this is an account by a former member of its systems team of a near-disaster at its only datacenter in New York. The machine room sat across the hall from the trading floor, in a skyscraper called 1 New York Plaza. It had an online UPS[1], CRAC units[2], refrigerator-sized network switches and about 10 rows of server cabinets.

Contractors cutting into materials in a nearby prep room kicked up dust, which set off the smoke alarm. The alarm was wired to shut down the CRAC units, so the room lost cooling while the ceiling sprinklers were filled with pressurized water, ready to spray once the air around them became very hot. The author ran to the office and pulled the power cables from every device in the room by hand. The temperature stopped climbing at 143.6 F, before it could pass the 150 F level he was trying to prevent.

Downtime was minimal because the major NYC markets were closed that day, and systems were back up the next morning. Afterward, the company kept the sprinklers and the machine room in its office building, but tightened procedures and surveillance. The Hong Kong team had noticed the overheating only by chance, when someone saw rising temperatures on a display across many servers, so the author set out to build a monitor that would ask each Linux server for its temperature and compute a mean.

Read the original michael.bacarella.comDiscussion

Discussion

Commenters mostly question the design: several say a physical emergency power off button and a link from the smoke alarms to the power would have been standard. Others point out that shutting down the cooling on smoke detection is not universal, since building codes allow an air handler serving only one space to keep running.

Sources

Published: First seen: Читать по-русски

Open as a page